Table 5 Line Mode Specifications MODEL IPS5000R IPS5000L Input Voltage Waveform Sinusoidal (utility or generator) Nominal Input Voltage 230Vac Low Line Disconnect 170Vac (Normal) 90Vac (generator/Wide range) Low Line Re-connect 180Vac (Normal) 100Vac (generator/Wide range) High Line Disconnect 280Vac High Line Re-connect 270Vac Max AC Input Voltage 300Vac rms Nominal Input Frequency 50Hz / 60Hz (Auto detection) Low Line Frequency Disconnect 40?1Hz Low Line Frequency Re-connect 42?1Hz High Line Frequency Disconnect 65?1Hz High Line Frequency Re-connect 63?1Hz Output Voltage Waveform As same as Input Waveform Output Short Circuit Protection Circuit Breaker 40A Efficiency (Line Mode) >95% Transfer Switch Rating 40A Transfer Time (AC to DC) 10ms (typical) 20ms (typical) Transfer Time (DC to AC) 10ms (typical) 20ms (typical) Power Limitation Input Voltage