        PRO803RS      
Capacity Volt-Amp
  • 3000 VA
     
Watt Standard Model
  • 2700 W
     
Long-Run Model
  • 2400 W
     
Phase
  • Single Phase In / Single Phase Out
Input
Voltage Range Low Line Transfer
  • 80/70/60/55VAC ±5% or 160/140/120/110VAC ±5% #1
Low Line Comeback
  • 85/75/65/60VAC ±5% or 170/150/130/120VAC ±5%
High Line Transfer
  • 150VAC ±5% or 300VAC ±5%
High Line Comeback
  • 140VAC ±5% or 290VAC ±5%
Frequency Range
  • 40~70Hz
Power Factor Correction
  • ≥ 0.99 @ nominal voltage (100%load)
Output
Output Voltage
  • 110/115/120/127VAC or 208/220/230/240VAC
AC Voltage Regulation (Battery Mode)
  • ±1%
Frequency Range Synchronized Range
  • 47~53Hz or 57~63Hz
Battery Mode
  • 50Hz ±0.2Hz or 60Hz ±0.2Hz
Current Crest Ratio
  • 5:1 (max.)
Harmonic Distortion Linear Load
  • ≤ 2% THD
Non-Linear Load
  • ≤ 8% THD
Transfer Time AC Mode to Battery Mode
  • Zero
Inverter to Bypass
  • Zero
Waveform (Battery Mode)
  • Pure Sinewave
Efficiency
AC Mode
  • 88%
 
Battery Mode
  • 85%
 
Battery
Standard Model Battery Type
  • 12V9AH
Numbers
  • 6
     
Typical Recharge Time
  • 4 hours recover to 90% capacity
Charging Current (max.)
  • 1A
Charging Voltage
  • 82.1VDC ±1%
     
Long-Run Model Battery Type Depending on applications
Numbers
  • 6
     
Charging Current (max.)
  • 4A/8A
Charging Voltage
  • 82.1VDC ±1%
     
Indicators
LCD Panel
  • UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, Fault Conditions
Alarm
Battery Model
  • Sounding every 4 seconds
Low Battery
  • Sounding every seconds
Overload
  • Sounding twice every seconds
Fault
  • Continuously sounding
Physical
Standard Model Dimension (mm) D×W×H
  • 600×438×88  [2U]
     
Net Weight (kgs)
  • 28
     
Long-Run Model Dimension (mm) D×W×H
  • 600×438×88  [2U]
     
Net Weight (kgs)
  • 13.8
     
Environment
Humidity
  • 20-90% Relative Humidity @ 0~40°C (Non-Condensing)
Noise Level
  • Less than 45dB @ 1 MeterLess than 55dB @ 1 Meter
Regulations
  • EN 62040-1:2008, EN 62040-2:2006, EN 61000-4-2:2009
MAnagement
Smart RS232
  • Support Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix and MAC