Automatic correction fuction
Large LED screen display
Heating/Cooling control
Digital communication
Temperature alarm
Product Name: RKC temperature controller
Model: REX-C100
Color: Black
Range :0-400 Celsius
Input: K
Power :100-240V AC, 50/60HZ
Size: 105 x 55 x 47mm
Main structure and function
* Self-correction function
* Large screen LED display
* Heating / cooling control
* Digital Communication
* Temperature alarm
Heater break alarm
Control loop break alarm
Product Description:
Input
a) thermocouple (TC): K, J, E, T, R, S, B, U, L, N, PL2, W5Re/w26Re
b) Thermal resistance (RTD): Pt100 JPT100
c) DC input: DC0 ~ 5V, DC1 ~ 5V, DC0 ~ 20mA, DC4 ~ 20mA
Requires connecting250W resistor between the terminals
Input Display Accuracy: (0.3% +1 bit of the setting value)
Input range: Refer to Input Range Table
Sampling period: 0.5sec
Process value bias -1999 ~ 9999 Celsius [° F] or -199.9 ~ 999.9 Celsius [° F] (temperature input)
±full scale (voltage / current input)
Setting range
a) the set value (SV): identical with temperature value range
b) heating side proportional band (P): 1 or 0.1 scale range (temperature input) x 0.1% to 100.0% scale range (voltage input)
c) Cooling side proportional band (Pc): 1% ~ 1000% heated side proportions
d) Integral time (I) :1-3600sec x 2
e) Derivative time (D) :1-3600sec x 3
f) Effective limited scope of the integral action (ARW): 1% -100% proportional band x 4
g) heating side proportional cycle 1-100sec x 5
h) Cooling side proportional cycle 1-100sec x 6
i) Senseless band: -10-10 or-10.0-+10.0 Celsius [° F] (temperature input)
-10.0 % - +10.0% of range (voltage / current input) x 7
* 1 If the proportional band is set to 0 Celsius [° F], ON-OFF action
* 2 If the integration time is set to 0sec, PD action
* 3 If the derivative time is set to 0sec, PI action
* 4 If the effective limited scope of the integral action is set to 0%, OFF
* 5 No need to set the current output circle
* 6 If the senseless band is set to a negative one, overlap
Control action
PID control (ON-OFF, P, PI, PD control)
a) automatic calculation function (AT)
① self-adjusting mode: limited cycle method
② AT cycle: 1.5
b) self-correction setting setting is changed, then the self-correction is established
* Excluding heating / cooling PID control action
Control Output
a) relay contact output: 250VAC 3A (with load) 1a connection
* Electrical: more than 300,000 times, the rated load
b) Voltage pulse output :0-12V DC (Load resistance: More than 600 Ω)
c) Current output: 4-20mA DC (load resistance: less than 600 Ω)
d) Thyristor control tube drive triggerring output: zero measurement, medium capacity drives
e) Thyristor control tube output: rated 0.5A (ambient temperature is below 40 Celsius)
Temperature alarm
Alarm point: Dual Alarm (set separately)
Alarm types: Deviation alarm (upper limit, lower limit, upper and lower limit, within the range)
Process value input alarm (upper limit, lower limit)
Setting value alarm (upper limit, lower limit)
* You can select a standby function (except the alarm setting value)
Control loop break alarm (LBA)
LBA set time: 0.1-200.0 min
* Can not be set to 0.0 min
LBA no sense with: 0-9999 Celsius [° F] (temperature input)
0 - range (voltage / current input)
* If set to 0, LBA does not operate.
Heater break alarm (HBA)
Input: current detection output
(RKC designated Model CTL-6-PN, CTL-12-S 56-10L-N)
Suitable scope: CTL-6-PN 0-30A CTL-12-S56-10L-N: 0-100A
Alarm Output
Relay contact output, 250V AC 1A (with load) 1a connection
* Off more than 50,000 times.
* Control loop break alarm output should be selected in one of the ALM1 or ALM2.
* When the control loop break alarm is selected, another alarm can't be set to LBA.
Communication functions (SCI)
Interface Standard: EIA RS-485
Protocol: ANSI X3.28 (1976) 2.5 A4
Communication Method: 2-wire half-duplex multi-station connection
Synchronization method: start / stop synchronization
Communication speed: 2400,4800,9600,19200 BPS
Digital start: 1
Data Digital: 7 or 8
Parity checking: with or without, such as "yes" when: Odd Number or Even Number
Stop bit: 1 or 2
The maximum number of connection points: 32 points (address setting 0-99)
Other
Power impact: no impact off the spreadsheet for 20ms or less
Off for more than 20ms, return to the initial state
Power data protection: do not disappear and support data
Ambient temperature: 0-50 Celsius [32-122 ° F]
Ambient humidity: 45-85% RH
Installation: embedded disk installation
1 x Temperature controller
1 x English user manual
Packed in carton