Introduction


XMT  Series  Intelligent  Temperature  Controller  adopts SCM for core which Micro anti-interference, large-capacity and advanced PID self-tuning method, and advance SMT technic, and the red/green double rows display measurement-value and setting-value at the same time.use advance components with software,

multipledigital filter technology,stable performance, higher measurement accuracy and strong

anti-interference. Various kinds of parameters can be set in the panel,  it can realize various classic or modern controlling technology like two digis, three digits, intelligent PID, and parameter auto-optimization& auto-adjusting according to different require, and is mainly uses in self-control system like  machines,chemical,ceramic,light industry,metallurgy petrifaction, petrochemical  and heat treatment.


Notice


--Thermal resistance or thermocoupleinput and measuring range both can be set freely.

--Softwareadjust zero and full scale, temperature measuring of cold-end alone, amplifier constant-zero display accuracy is better than 0.2%FS.

--The method of fuzzy theory combine with the traditional PID makes the temperature be controlled quickly and smoothly.

--The method of advanced PID parameter self-tuning saves a third time as compared with ordinary instrument.

--The output signal is optional: relay output, DC12V driver solid state relay, 4-20mA current

--Alarm output: two circuit user-defined alarm output.

Model

 XMTE-2581

Max Load Current

60mA  

Input Specifications

K.(J).E.Pt100(set freely)

Output Signal

DC12V  Voltage output

Temp Control Range

(0-400 default)K(0-1350℃) ,J(0-1000℃) ,E(0-1000℃),Pt100(-200-650℃)

Precision

0.5 class(±0.5%F+1)

Sampling Rate

Twice per second

Regulating Methods

Intelligent PID control, according to the value of P,I,D parameters, we can get P(P=0 is on-off control),PI,PD,PID regulating mode

Alarm function (optional)

One upper limit Alarm Alarm acts when at deviation of 10  (changable)

Power supply

Transformer AC220V±10%

Power Consumption

≤3VA

Contact Capacity

AC250V 2A (Resistive Load)

Contact Life

>10x104 times

Main Usage

Controlling temperature of ON/OFF in SSR SSR-DA,SSR3-DA    

General Information

Ambient temperature

-10-50℃

Relative humidity: