Introduction


XMT  Series  Intelligent  Temperature  Controller  adopts SCM for core which Micro anti-interference, large-capacity and advanced PID self-tuning method, and advance SMT technic, and the red/green double rows display measurement-value and setting-value at the same time.use advance components with software,

multipledigital filter technology,stable performance, higher measurement accuracy and strong

anti-interference. Various kinds of parameters can be set in the panel,  it can realize various classic or modern controlling technology like two digis, three digits, intelligent PID, and parameter auto-optimization& auto-adjusting according to different require, and is mainly uses in self-control system like  machines,chemical,ceramic,light industry,metallurgy petrifaction, petrochemical  and heat treatment.


Notice


--Thermal resistance or thermocoupleinput and measuring range both can be set freely.

--Softwareadjust zero and full scale, temperature measuring of cold-end alone, amplifier constant-zero, display accuracy is better than 0.2%FS.

--The method of fuzzy theory combine with the traditional PID makes the temperature be controlled quickly and smoothly.

--The method of advanced PID parameter self-tuning saves a third time as compared with ordinary instrument.

--The output signal is optional: relay output, DC12V driver solid state relay, 4-20mA current

--Alarm output: two circuit user-defined alarm output.


ModelXMTG-2591
Max Load Current60mA
Input SpecificationsK.(J).E.Pt100(setfreely)
Output SignalDC12V Voltage output
Temp Control Range(0-400℃ default)K(0-1350℃) ,J(0-1000℃) ,E(0-1000℃),Pt100(-200-650℃)
Precision 0.5class(±0.5%F+1)
Sampling RateTwiceper second
Regulating MethodsIntelligentPID control, according to the value of P,I,D parameters, we can get P(P=0 ison-off control),PI,PD,PID regulating mode
Alarm function (optional)One lower limit Alarm Alarm acts when at absolute value of 100  (changable)
Power supplyTransformerAC220V±10%
Power Consumption≤3VA
ContactCapacityAC250V2A (Resistive Load)
Contact Life>10x104 times
Main UsageControllingtemperature of ON/OFF in SSR SSR-DA,SSR3-DA
General Information
Ambient temperature-10-50℃
Relative humidity≤85%RH(non-corrosive)
Storage temperature-25~75℃
Dimension48*48*90mm
Mounting size45*45mm
InstallationModePanelType
Waterproof levelIP67