Key Features

 

Applications

 
 
Product Features 
 
Model          PRO806RS  
Capacity Volt-Amp
  • 6000 VA
 
Watt Standard Model
  • 5400 W
 
Long-Run Model
  • 5400 W
 
Phase
  • Single Phase In / Single Phase Out
Input
Voltage Range Low Line Transfer
  • 176 VAC ±3% @ 100% Load or 110 VAC ±3% @ 50% Load
Low Line Comeback
  • 186 VAC ±3% @ 100% Load or 120 VAC ±3% @ 50% Load
High Line Transfer
  • 300VAC ±3%
High Line Comeback
  • 290VAC ±3%
Frequency Range
  • 46~54Hz or 56Hz~64Hz
Power Factor Correction
  • ≥ 0.99 @ 100% Load
Output
Output Voltage
  • 208/220/230/240VAC
AC Voltage Regulation (Battery Mode)
  • ±1%
Frequency Range Synchronized Range
  • 46~54Hz or 56~64Hz
Battery Mode
  • 50Hz ±0.1Hz or 60Hz ±0.1Hz
Current Crest Ratio
  • 3:1
Harmonic Distortion Linear Load
  • ≤ 2% THD
Non-Linear Load
  • ≤ 6% THD
Transfer Time AC Mode to Battery Mode
  • Zero
Inverter to Bypass
  • Zero
Waveform (Battery Mode)
  • Pure Sinewave
Efficiency
AC Mode
  • 90%
Battery Mode
  • 88%
Battery
Standard Model Battery Type
  • 12V7AH
 
Numbers
  • 20
 
Typical Recharge Time
  • 9 hours recover to 90% capacity
Charging Current (max.)
  • 1A
Charging Voltage
  • 273VDC ±1%
Long-Run Model Battery Type Depending on applications
Numbers
  • 20
Charging Current (max.)
  • 4A
Charging Voltage
  • 273VDC ±1%
Indicators
LCD Panel
  • UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, Fault Conditions
Alarm
Battery Model
  • Sounding every 4 seconds
Low Battery
  • Sounding every seconds
Overload
  • Sounding twice every seconds
Fault
  • Continuously sounding
Physical
Standard Model Dimension (mm) D×W×H
  • UPS Unit : 580×438×133 [3U]
    Battery Pack : 580×438×133 [3U]
 
Net Weight (kgs)
  • UPS Unit : 17
    Battery Pack : 57
 
Long-Run Model Dimension (mm) D×W×H
  • 580×438×133 [3U]
 
Net Weight (kgs)
  • 17
 
Environment
Humidity
  • 20-90% Relative Humidity @ 0~40°C (Non-Condensing)
Noise Level
  • Less than 45dB @ 1 MeterLess than 55dB @ 1 Meter
Regulations
  • EN 62040-1:2008, EN 62040-2:2006, EN 61000-4-2:2009
MAnagement
Smart RS232