Key Features

 

Applications

 
Products Specifications 
 
 
Model
  • PRO8015L
Capacity Volt-Amp
  • 1500VA
Watt
  • 1200w
Phase
  • Single Phase In / Single Phase Out
Isolation Transformer
  • Optional
Input
Voltage Range Low Line Transfer
  • 160VAC ±5% or 80VAC ±5% @ 100% Load
    110VAC ±5% or 50VAC ±5% @ 50% Load
Low Line Comeback
  • 175VAC ±5% or 85VAC ±5% @ 50% Load
High Line Transfer
  • 300VAC ±5% or 150VAC ±5%
High Line Comeback
  • 290VAC ±5% or 145VAC ±5%
Frequency Range
  • 40~70Hz
Power Factor Correction
  • ≥ 0.99 @ nominal voltage (100%load)
Output
Output Voltage
  • 208/220/230/240VAC or 110/115/120/127VAC
AC Voltage Regulation (Battery Mode)
  • >±3%
Frequency Range Synchronized Range
  • 47~53Hz or 57~63Hz
Battery Mode
  • 50Hz ±0.25Hz or 60Hz ±0.3Hz
Current Crest Ratio
  • 3:1
Harmonic Distortion Linear Load
  • ≤ 3% THD
Non-Linear Load
  • ≤ 6% THD
Transfer Time AC Mode to Battery Mode
  • Line Mode: Zero
Inverter to Bypass
  • Line Mode: 4ms (Typical)
Waveform (Battery Mode)
  • Pure Sinewave
Power Factor
  • 0.8
Efficiency
AC Mode
  • 85%
Battery Mode
  • 83%
ECO Mode
  • 97%
Battery
Standard Model Battery Type
  • 12V7AH
Numbers of Battery
  • 3
Typical Recharge Time
  • 4 hours recover to 90% capacity
Charging Current (max.)
  • 1A
Charging Voltage
  • 41.0VDC ±1%
Long-Run Model Battery Type
  • Depending on Applications
Numbers of Battery
  • 3
Charging Current (max.)
  • 8A
Charging Voltage
  • 41.0VDC ±1%
Indicators
LCD Panel
  • UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, Fault Conditions
ALARM
Battery Model
  • Sounding every 4 seconds
Low Battery
  • Sounding every seconds
Overload
  • Sounding twice every seconds
Fault
  • Continuously sounding
Physical
Standard Model Dimension (mm) D×W×H
  • 397×145×220
Net Weight (kgs)
  • 13
Long-Run Model Dimension (mm) D×W×H
  • 397×145×220
Net Weight (kgs)
  • 7
Environment
Humidity
  • 20-90% Relative Humidity @ 0~40°C (Non-Condensing)
Noise Level
  • Less than 45dB @ 1 MeterLess than 55dB @ 1 Meter
Regulations
  • EN 62040-1-1:2003, EN 62040-2:2006, EN 61000-2-2:2002, EN 61000-4
Management
Smart RS232
  • Support Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix and MAC
Package Content

Included

  • Please contact regional sales staff for details.