Key Features 

 

Applications


 
Product Specifications 
 
Model
  • PRO806S
     
Capacity Volt-Amp
  • 6000 VA
     
Watt
  • 4800 W
     
Phase
  • Single Phase In / Single Phase Out
Isolation Transformer
  • Optional
 
Voltage Range Low Line Transfer
  • 176VAC ±3% @ 100% Load
    110VAC ±3% @ 50% Load
 
High Line Transfer
  • 300VAC ± 3% 
 
High Line Comeback
  • 290VAC ± 3%
 
Frequency Range
  • 46~54Hz (Auto Sensing)
Power Factor Correction
  • ≥ 0.99 @ 100% Load
   
 
Output AC Voltage
  • 208 VAC
AC Voltage Regulation (Battery Mde)
  • ±1%
 
Frequency Range Synchronized Range
  • 47~53Hz or 57~63Hz
Battery Mode
  • 50Hz ±0.1Hz or 60Hz ±0.1Hz
Current Crest Ratio
  • 3:1
Harmonic Distortion Linear Load
  • ≤3% THD
   
Non-Linear Load
  • ≤6% THD
   
Transfer Time AC Mode to Battery Mode
  • Zero
Inverter to Bypass
  • Zero
Waveform (Battery Mode)
  • Pure Sinewave
Power Factor
  • 0.8
 
AC Mode
  • 89%
     
Battery Mode
  • 88%
     
 
Standard Model Battery Type
  • 12V9AH
 
Numbers
  • 20
     
Typical Recharge Time
  • 7 hours recover to 90% capacity
Charging Current (max.)
  • 4A
Charging Voltage
  • 273VDC ±1%
     
 
LCD Panel
  • UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, Fault Conditions
Alarm
Battery Model
  • Sounding every 4 seconds
Low Battery
  • Sounding every seconds
Overload
  • Sounding twice every seconds
Fault
  • Continuously sounding
 
Standard Model Dimension (mm) D×W×H
  • 592×250×576M
     
Net Weight (kgs)
  • 81
     
Long-Run Model Dimension (mm) D×W×H
  • 592×250×576
     
Net Weight (kgs)
  • 25
     
 
 
Smart RS232
  • Support Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix and MAC